Flue Gas Headers
Flue Gas Headers for Vitodens 200 installation in series.
Notes:
The flue system is tested and CE designated to EN 14471.
In accordance with FeuVo [or local regulations], install condensing boilers from 50 kW rated heating output in a separate ventilated installation room with a suitable vent.
The unrestricted cross-section must be at least 150 cm² and should be 2 cm² larger for each additional kW rated heating output above 50 kW.
Observe information in the technical guide and the TRGI 1986/96.